Enersys NSB 100FT BLUE+ Battery
Thin Plate Lead Carbon
NorthStar Enersys NSB 100FT BLUE+ delivers ultra fast recharge and exceptional PSoC cycling performance.
Features
- Exceptional PSoC cyclic performance 2050 cycles @50% DoD
- Design life 12+ years at 20°C (68°F)
- EUROBAT design life definition: Very Long Life (12+ years)
- Ultra fast recharge
- Shelf life of up to 24 months
- High modulus Polyphenylene Oxide (PPO) plastic materials designed to withstand extended elevated operating temperatures and maintain high battery compression essential for reliable operation
- Flame retardant (UL 94 VO) and LOI of at least 28%
- Lead carbon added to negative electrodes increases power and reduces sulfation
- High potential fuel savings when used with hybrid genset applications
- Operating temperature range -40°C to +65°C (-40°F to 149°F)
- State-of-the-art automated manufacturing ensures consistency and reliability
- Advanced 3 stage terminal design to ensure leak-free operation – brass terminals provide maximum performance
- Non-halogenated thermally sealed plastic casing
- Approved as non-hazardous cargo for ground sea and air transport DOT 49CFR173.159(d), (i) and (ii)
Specifications
Terminal | Female M8 x 1.25 |
---|---|
Terminal torque | 8.0 Nm (71 in-lbs) |
10 hr capacity to 1.80VPC @ 25°C (77°F) | 100 Ah |
8 hr capacity to 1.75VPC @ 25°C (77°F) | 100 Ah |
Float voltage @ 20/25°C (68/77°F) | 2.28 / 2.27 VPC |
Impedance (1Khz) | 2.6 mΩ @ 25°C (77°F) |
Conductance | 1846 S |
Short circuit current | 3500 A |
Maximum charge current (A) | No Limit |
Operation temperature range | -40°C to +65°C |
Nominal voltage | 12 V |
All NorthStar batteries are compliant with: Telcordia SR4228, IEC 60896; Bellcore GR-63-Core, Issue 1; British, German, and Russian telecom standards; UL approved and UN2800 certified. NorthStar is registered to ISO 9001 and ISO 14001. Please refer to Data Sheet for additional specifications.