Westell N250140-NCY-M3 Fuse Panel
Dual Bus, Negative Voltage, for -24 or -48VDC, 19″/23″ rack , 1 RU, 40 GMT/Panel, 20 GMT/Bus, 200 Amps/Panel, input Block two 1/4″ studs, Output #26 AWG to 14 AWG, Alarm Connection Wire wrap, Nebs level 3, Earthquake Zone 4
Westell’s N250140-NCY-M3 Fuse Panel provides up to 40 circuits for the distribution of DC power to equipment. Each of the 40 circuits is individually protected by a GMT style telecommunication fuse located on the panel’s faceplate. Alarm circuits are provided to indicate and extend alarm conditions when faults occur.
- Negative (-) VDC input voltage, -24 or –48Vdc
- Without diodes this panel can operate at 200 Amps of output current per panel (100 Amps per Bus)
- With diodes the panel will operate at 60 Amps of output current per panel (30 Amps per Bus)
- 2 Isolated battery returns
- Green power LEDs provided for each bus
- Common (C), normally closed (NC), normally open (NO) alarm extensions (2 sets of dry form “C” contacts)
- Both GND and – BATTERY activated external alarms (alarms that originated outside panel)
- Single 1.75” mounting height (single panel space)
- Brackets supplied are reversible for both 19″ and 23″ racks and 1.75″ mounting spaces
- NEBS Certification is not available in diode equipped panels
Please refer to Data Sheet for additional specifications.